Installation Manual
PNEU-DD-IOM-1.0 8-9-02
Dual Duct Models with TITUS II and IIA Pneumatic Controls
Installation, Operation, and Maintenance Manual
Adjusting Minimum and Maximum Air Flow for Units with Two Inlet Sensors
A. Maximum Flow Adjustment for
Direct Acting Thermostat
1. Be sure the minimum LO air ow
limit is zero on hot and cold deck
controller.
2. To adjust the cold deck maximum
CFM:
a. A pply 15- 25 PSI t o t h e
thermostat connection on the
cold deck controller. Place a
manometer gauge a c r o s s
balancing tees at the cold deck
inlet.
b. If the manometer gauge
reading matches the r equired
dierential from the calibration
curv e (Page 6 and 7) n o
adjustment is necessary.
c. If adjustment is necessary, use
the adjusting tool stored in the
face of the controller (Titus II
only) or a standard at blade
screwdriver.
d. Rotate the maximum HI knob
slowly. A delay in response
time has been deliberately built
into the controls t o a v oid
hunting. Allow several sec onds
for the controls to react and the
system to stabilize. Rotate the
knob until the gauge shows the
required dierential pressure.
N O T E : I f t h e actuator fails t o
respond, see G u ide to Ser v ice
Procedures.
3. To adjust the hot deck maximum
CFM:
a. Appl
y 0 PSI to the thermostat
connection on the cold dec k
controller. That is, leave it open to
the atmosphere.Place a manometer
gauge across balancing tees at the
cold deck inlet.
b. Repeat Steps B, C and D above.
B. Maximum Flow Adjustment for
Reverse Acting Thermostat
1. To adjust the cold deck maximum
CFM:
a. Apply 0 PSI to the thermostat
connection on the cold deck
controller. That is, leave it open
to the atmosphere. Place a
manometer gauge a c r o s s
balancing tees at the cold deck
inlet.
b. Re peat steps B, C and D
above.
2. To adjust the hot deck maximum
CFM:
a. A pply 15- 25 PSI t o t h e
thermostat connection on the
hot deck. Place the manometer
gauge across balancing tees at
the hot deck inlet.
b. Re peat steps B, C and D
above.
C. Minimum Flow Adjustment for
Either Thermostat
1. Place a 0-30 PSI pressure gauge in
the line between the TITU S I I
Controller and the damper actuator
on the cold deck.
2. Place a manometer gauge across
the balancing tees on the hot deck
inlet.
3. Adjust the thermostat pressure
(Pressure reducing v a l v e
recommended) until the cold deck
damper just closes:
a. If t
he damper in the cold deck
is normally open, the pressure
gauge should read
approxima t ely 10 PSI with
standard 5-10 PSI actuator.
b. If the damper in the cold deck
is normally closed, t h e
pressure gauge should read
approximately 5 PSI w i t h
standard 5-10 PSI actuator.
4. Refer to Page 6 a nd 7 f o r t h e
dierential pressure corresponding
to the desired minimum air ow
(CFM).
5. Adjust the reset start point dial on
the hot deck until the manometer
gauge across the balancing tees
on the hot deck reads the desired
dierential pressure.
D. After Flow Rates are Adjusted
1. Replace the thermostat connection
at the controller, if it has been
removed during the adjustment
process.
2. Remove the m anometer gauge and
replace the caps on the tees in the
HI and LO tubes.
NOTE: The controller w ill not operate
if these caps are left o.
3. Return the adjustment tool to its
socket in the face of the controller.
4. R eplac e t he cov e r s o v e r t h e
controllers.
B
Cold
TSTAT
MAIN
M
T
Hi
Lo
B
Hot
Hi
Lo
M
T
Figure 1. Piping Diagram Figure 2. Control Box Label
MODEL NO. PEDV SIZE: 6
MAX CFM: 400 MIN CFM: 0
COLD INLET CFM: 400 VP: 0.63
HOT INLET CFM: 400 VP: 0.63
HAND (COLD INLET LOCATION):RH
LOCATION: XXXX
FACTORY NO. XXXX ITEM: XXXX
MOTOR: XXXX
THST: DIRECT ACTING
Inlet Size, Inches
Minimum CFM
Cold Deck Max Velocity Pressure, Inches WG
Hot Deck Max Velocity Pressure, Inches WG
Same as Number as on Packing List
Actuator Mfr.
Thermostat Action
Seitenansicht 0
1 2 3 4 5 6 7 8 9

Inhaltsverzeichnis

Seite 1 - Installation Manual

Installation ManualPNEU-DD-IOM-1.0 8-9-02Dual Duct Models with TITUS II and IIA Pneumatic ControlsInstallation, Operation, and Maintenance ManualAdjus

Seite 2 - PNEU-DD-IOM-2.0 8-9-02

CONTROLLERT MMLOBACTUATORT HiHotColdACTUATORCONTROLLERLoMBHiTPNEU-DD-IOM-2.0 8-9-02Adjusting Minimum and Maximum Air Flow for Units with Hot Inlet Sen

Seite 3 - Hot Inlet Sensor Calibration

PNEU-DD-IOM-3.0 8-9-02Hot Inlet Sensor Calibration2. Cold inlet controller / dischargesensor. For Constant Air Volume.To adjust until Total CFM:a. If

Seite 4 - CONTROLLER

MTACTUATORACTUATORCONTROLLERTMHiBLOColdHotCONTROLLERMLoTHiBPNEU-DD-IOM-4.0 8-9-02Adjusting Minimum and Maximum Air Flow for Units with Cold Inlet Sens

Seite 5 - Cold Inlet Sensor Calibration

PNEU-DD-IOM-5.0 8-9-02Cold Inlet Sensor Calibration2. Hot inlet controller / dischargesensor. For Constant Air Volume.To adjust until Total CFM:a. If

Seite 6 - INLET DIAMETER (INCHES)

PNEU-DD-IOM-6.0 8-9-02AeroCrossTM Multi-Point Inlet SensorOriginal Titus Multi-Point Inlet Sensor (for use with units shipped before April 1, 2002)Fig

Seite 7

6"500INLET SENSOR DIFFERENTIAL (IN. W.G.)0.040.03504070200100300400CFMINLET DIAMETER (INCHES)0.40.30.20.070.050.11.00.70.55"4"300070010

Seite 8

PNEU-DD-IOM-8.0 8-9-02Guide to Service ProceduresActuator will not stroke. (Generally any settingof the damper compatibility selector on the faceof th

Seite 9 - PNEU-DD-IOM-9.0 8-9-02

PNEU-DD-IOM-9.0 8-9-02Replacement PartsActuatorsKrueter MCP-8031 (5-10PSI) 10058501Johnson D-3062 (5-10PSI) 10058601Actuator Crank ArmsKrueter 3019200